Compressor valves control the intake and discharge of refrigerant gas. A leaking or broken valve changes how the compressor pumps and what it reads.
Suction and discharge valves
A leaking discharge valve lets high-pressure gas back into the cylinder, reducing capacity and raising discharge temperature. A leaking suction valve reduces pumping efficiency. Both show as equalising pressures and low amps under load.
Diagnosis at a glance
Symptoms of failure
- •Reduced capacity
- •High discharge temperature
- •Equalising pressures
- •Low amps under load
Measurements to take
- •Pump-down test
- •Discharge temperature
- •Pressures and amps